Note: The following functions are a continuation from the previous page. These functions can only be
displayed and must have their settings changed using another programming method referenced later in
the manual. As the other programming method requires turning the UPS off to perform, they are
accessible here as a convenient reference while the UPS is in normal online operation.
The next parameter displayed
shows the “bypass input
voltage acceptable window”
setting. The voltage window
can be set to “Lo” (184-260Vac)
or “Hi” (195-260Vac), which is
shown below.
Depress the “Next Page”
button.
The next parameter displayed
shows acceptable input
frequency window. The window
can be set to +/-3Hz (shown), or
+/-1Hz (not shown).
Depress the “Next Page”
button.
The next parameter display is
the inverter output voltage
setting. The inverter output
voltage can be set to 200Vac
(not shown), 220Vac (shown),
230Vac (not shown) or 240Vac
(not shown).
Depress the “Next Page”
button.
The following V1, V2, V3 and V4
show the operational status
setting of the UPS. This
function may be set to one of
four modes. “Normal”
indicates none of the other
modes are set.
Economy/Green Mode:
Indicates the UPS will
automatically transfer to
bypass mode to save energy,
one minute after the output
load drops below 10% of the
UPS output rating.
25