FieldServer FS-8700-39 Computer Drive User Manual


 
FS-8700-39 EST3 Driver Manual Page 17 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix C. EST3 Data Format:
Appendix C.1. Input data format
Each input device is associated with a 16-bit value. The contents of the 16 bits are used to generate
status types as shown in the table below. Each incoming event is allocated to a status type
depending on its device type as shown in the table. It is possible to override this default status type
allocation. Refer to Appendix A.5 for more information.
Type Encode
Value
Alarm
Trouble
Supervisory
Monitor
Others
Smoke 0 Y
Pull 1 Y
Heat 2 Y
Waterflow 3 Y
Stageone 4 Y
Zone 5 Y
AlarmVerify 6
Y
PreAlarm 7
Y
Security 8
Y
Station 9
Y
Emergency 10
Y
Supervisory 11
Y
Valve 12
Y
GateValve 13
Y
Tamper 14
Y
Temperature 15
Y
Power 16
Y
Signal 17
Y
TroubleOpen 18
Y
TroubleShort 19
Y
LocalTrouble 20
Y
MaintAlert 21
Y
DirtyHead 22
Y
DeviceComm 23
Y
GroundFault 24
Y
InternalTrouble 25
Y
BadType 26
Y
BadPersonality 27
Y
UnexpectedDevice 28
Y
CommonTrouble 29
Y
RelayConfirmation 30
Y
Monitor 31
Y
LocalMonitor 32
Y
Damper 33
Y
Fan 34
Y
Door 35
Y
Switch 36
Y
FirePhone 37
Y