FieldServer FS-8700-39 Computer Drive User Manual


 
FS-8700-39 EST3 Driver Manual Page 7 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where data
is to be stored in the FieldServer
One of the Data Array names
from “Data Array” section above
Data_Array_Offset Starting location in Data Array
0 to maximum specified in “Data
Array” section above
Function Function of Client Map Descriptor
RDBC, WRBC
3
, WRBX
4.4.2. Driver Related Map Descriptor Parameters
Column Title Function Legal Values
Node_Name Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor” above
EST_Panel Panel 0 - 63
EST_Card Card 0 - 255
Address Starting address of read block 0 - 1023
Length Length of Map Descriptor
For Reads: 1 to 34 For Writes:
1
EST_Object_Type Object type parameter
Relay, Led, ServGroup,
GuardPtrl, ChkInGrp,
AltMessage, Reset, PanelSil,
AlarmSil, Drill, GAInhibit,
Reboot, Evacuate, AltSensitiv,
Partition, CmdList, Input, Zone,
Card, AndGroup, Matrix,
TimeCtrl, InstructionText,
AmpPower, AudMsg, CmdList,
MCmsg, SetDate, SetTime
EST_Index Index parameter 0 - 65535
EST_Route Route parameter 0 - 255
EST_Priority Pri parameter 0 - 4 (see note below)
EST_Chan Chan parameter 0 - 255
EST_Msg_Index MsgIndex parameter 0 - 65535
EST_Account Account parameter 0 - 255
EST_ConfCL ConfCL parameter 0 - 65535
EST_Panel_Mask_1 PanelMask(1) parameter (LSB) 0 - 255
EST_Panel_Mask_2 PanelMask(2) parameter 0 - 255
EST_Panel_Mask_3 PanelMask(3) parameter 0 - 255
EST_Panel_Mask_4 PanelMask(4) parameter 0 - 255
EST_Panel_Mask_5 PanelMask(5) parameter 0 - 255
EST_Panel_Mask_6 PanelMask(6) parameter 0 - 255
EST_Panel_Mask_7 PanelMask(7) parameter 0 - 255
EST_Panel_Mask_8 PanelMask(8) parameter (MSB) 0 - 255
Data_Array_Low_Scale* Scaling zero in Data Array
-32767 to 32767, 0
Data_Array_High_Scale*
Scaling max in Data Array
-32767 to 32767, 100
Node_Low_Scale* Scaling zero in Connected Node
-32767 to 32767, 0
Node_High_Scale* Scaling max in Connected Node
-32767 to 32767, 100
3
WRBC is not recommended, as startup values may be invalid