Appendix E. Driver Error Messages
Error Message Description and Action Required
EST3:#01 FYI. For an
Old EST3 Panel, Read
MD length must be even.
This message will be displayed once if any Map Descriptor in a configuration
file has an odd length. Old EST3 Panels (before 2002) simply do not
communicate if length is odd.
This message can be ignored if it is new EST3 panel. But if it is old or
unknown, try making Map Descriptor having even length before contacting
technical support.
EST3:#02 Err. Read MD
length must > 0 and <=
%d
Numbers of addresses to be read per request are limited.
Edit configuration file to set Map Descriptor length within specified range.
6
EST3:#03 Err. Write MD
must have length = 1
One Map Descriptor can write only 1 value. Change length to 1
6
.
EST3: #04 Unknown
Escape Sequence 1B
%02X considered as
%02X
This message is printed if the FieldServer receives sequences that are not
specified. Specified sequences are 1B 82, 1B 8D and 1B 9B. This message
is for information only and can be ignored unless the data stored by the
FieldServer is invalid in which case, call Tech support.
6
Download the configuration file, make the necessary changes, upload to the FieldServer and cycle
power to the FieldServer for the changes to take effect.