FieldServer FS-8700-39 Computer Drive User Manual


 
FS-8700-39 EST3 Driver Manual Page 3 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
1. EST3 Description
The EST3 External Communications Protocol (ECP) driver allows the FieldServer to transfer data to
and from EST devices over RS-232 or RS-485 (with converter) serial ports using the EST3 ECP
protocol. In the EST application the FieldServer always emulates a Client.
The FieldServer makes use of the following ECP Services:
Read Operations:
Report Service
Delta Service
Write Operations:
Command Service
All read points are continually updated using the Report Service; response times are enhanced using
Delta Service broadcasts by the EST3 panel.
The information that follows describes how to expand upon the factory defaults provided in the
configuration files included with the FieldServer.
2. Driver Scope of Supply
2.1. Supplied By FieldServer Technologies for this Driver
FIELDSERVER
TECHNOLOGIES PART #
DESCRIPTION
FS-8915-10 7’ Patch Cable
FS-8917-03 RJ45 to DB9M Connector adapter
FS-8917-10 DB9F to terminal Adapter
FS-8700-39 EST3 ECP Driver Manual
2.2. Provided By the Supplier of 3
rd
Party Equipment
2.2.1. Hardware
PART # DESCRIPTION VERSION
EST3 Gateway
2.2.2. Required 3
rd
Party Configuration
The EST3 panel has to be set into the “Gateway Mode” using the EST3 Configuration tool (3-
SDU)
Possible Protocols
ECP Type II Supported
ECP Type II with Text Not Supported
ECP Type III Supported
ECP Type III with Text
Not Supported