4.5.2. VESDA data format for command 4 (Zone Update)
This request returns the Current Zone Status in a BIT data array. The format for the data
is as follows:
Data Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Up to 15 alphanumeric
characters
Data_Format Provides data format BIT
Data_Array_Length Number of Data Objects 1 - 16
Client Side Map Descriptors
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where
data is to be stored in the
FieldServer
As above.
Data_Array_Location
Starting location in Data
Array
0 -16
Function
Function of Client Map
Descriptor.
RDBC
Node_Name
Name of Node to fetch data
from
One of the node names
specified in “Client Node
Descriptor” above
Data_Type Data type dig_input
Length Length of Map Descriptor
1-16 (must not overflow the
data array)
Address
Starting address of read
block
1-16
Command
The command id as given in
the notes.
4
Network The network number 1-255
Zone The zone number 1-255
Sector The sector number 1-255
Data Block Description
2
BIT offset Function BIT offset Function
0 Other Zone Info 8 Fault Power
1 Scanning 9 Fault Urgent
2 Autolearning 10 Fault Zone
3 Normalising 11 Fault System
4 Isolated 12 Alarm Fire2
5 Fault Filter 13 Alarm Fire1
6 Fault Airflow 14 Alarm Action
7 Fault Network 15 Alarm Alert
2
1 indicates TRUE; 0 indicates FALSE