FS-8700-43 VESDA Driver Manual Page 6 of 18
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4. Configuring the FieldServer as a VESDA Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Vesda Server.
4.1. Data Arrays
The configuration file tells the FieldServer about its interfaces, and the routing of data
required. In order to enable the FieldServer for Vesda communications, the driver
independent FieldServer buffers need to be declared in the “Data Arrays” section, the
destination device addresses need to be declared in the “Client Side Nodes” section, and
the data required from the servers needs to be mapped in the “Client Side Map Descriptors”
section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
Section Title
Data_Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Up to 15 alphanumeric
characters
Data_Format Provides data format BIT,FLOAT,BYTE
Data_Array_Length Number of Data Objects 1-10000
Example:
// Data Arrays
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
set_op, bit, 32
VESDA01_1_f, float, 32
VESDA01_1_b, bit, 32
VESDA01_2_f, float, 32
VESDA01_2_b, bit, 32
VESDA01_3_f, float, 32
VESDA01_3_b, bit, 32
VESDA01_4_f, float, 32
VESDA01_4_b, bit, 32