FieldServer FS-8700-43 Computer Drive User Manual


 
FS-8700-43 VESDA Driver Manual Page 8 of 18
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where
data is to be stored in the
FieldServer. Only used for
commands 1,4,6,12.
One of the Data Array
names from “Data Array”
section above. Must be of
type BIT
Data_Array_Location Starting location in Data Array
0 to maximum specified in
“Data Array” section above
Function
Function of Client Map
Descriptor. A Command is a
write, and a response is a read
RDBC, WRBC, WRBX
4.4.2. Driver Related Map Descriptor Parameters
Column Title Function Legal Values
Node_Name Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor” above
Data_Type Data type Dig_input or dig_output
Length Length of Map Descriptor 1 to end of data block or less
Address Starting address of read block
The start bit number of the data
of interest
Command
The command id as given in the
notes.
1,4,6,10,12,16
Network The network number 1-255
Zone The zone number
1-255 or 0 if the Zone is not
configured on the Panel
Sector The sector number
1-255 or 0 to read the average
smoke level and highest alarms.
DA_Bit_Name
Name of Data Array where data
is to be stored in the FieldServer.
Used for command 10 and 16.
One of the Data Array names
from “Data Array” section above.
Must be of type BIT
DA_Bit_offset
Starting location in Data Array.
Used for command 10 and 16
0 to maximum specified in “Data
Array” section above
DA_Float_Name
Name of Data Array where data
is to be stored in the FieldServer.
Only used for command 10.
One of the Data Array names
from “Data Array” section above.
Must be of type FLOAT
DA_Float_offset
Starting location in Data Array.
Only used for command 10
0 to maximum specified in “Data
Array” section above
DA_Byte_Name
Name of Data Array where data
is to be stored in the FieldServer.
Only used for command 16.
One of the Data Array names
from “Data Array” section above.
Must be of type BYTE
DA_Byte_offset
Starting location in Data Array.
Only used for command 16
0 to maximum specified in “Data
Array” section above