4.2. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Protocol Specify protocol used VESDA
Example:
Nodes
Node_name, Protocol, Port, Timeout, Recovery_Interval, Retry_Interval
VESDA_HLI, VESDA, P1, 10.0s, -, -
4.3. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device
is connected to the FieldServer
P1-P8, R1-R2
1
Baud Specify baud rate 19200
Parity Specify parity None
Data_Bits
Specify data bits 8
Stop_Bits Specify stop bits 1
Timeout Message timeout 10s
IC_timeout Inter character timeout 1.0s
Example:
// Client Side Connections
//
Connections
Port, Baud, Timeout, IC_Timeout, Parity, Data_bits, Stop_bits
P1, 19200, 10.0s, 1.0s, none, 8, 1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.