4.4.3. Map Descriptor Example
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Data_Type, Node_Name, Address, Length, Command, Network, Zone, Sector
set_op_vesda_hli, set_op, 0, WRBC, dig_output, VESDA_HLI, 0, 8, 1, 0, 255, -
Map_Descriptors
Map_Descriptor_Name, Zone, Sector, node_name, Function, DA_Bit_Name DA_Float_Name, DA_Bit_offset, DA_Float_offset, Data_Array_Offset, Data_Type, Command, Network, Address, Length
rd_vesda_01_1, 0, 128, VESDA_HLI, rdbc, VESDA01_1_ VESDA01_1_f, 0, 0, 0 dig_input, 10, 0, 0, 32
rd_vesda_01_2, 0, 64, VESDA_HLI, rdbc, VESDA01_2_b VESDA01_2_f, 0, 0, 0 dig_input, 10, 0, 0, 32
rd_vesda_01_3, 0, 32, VESDA_HLI, rdbc, VESDA01_3_b VESDA01_3_f, 0, 0, 0 dig_input, 10, 0, 0, 32
rd_vesda_01_4, 0, 16, VESDA_HLI, rdbc, VESDA01_4_b VESDA01_4_f, 0, 0, 0 dig_input, 10, 0, 0, 32