FieldServer FS-8700-59 Computer Drive User Manual


 
FS -8700-59 Canatal Sachnet Driver Manual
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 12
6. Driver Notes
6.1 Canatal Device Data Tables
Canatal Devices's have their data organized into data tables. A query requests a number of
elements from a particular data table. The number, length and contents of the data tables is
defined by the Canatal Corporation and is dependent on the series number of the device being
addressed.
You will need to be familiar with the data tables you with to poll using this driver.
The following table specifies the series and tables that can be polled / written to / emulated to this
driver.
Series Table Data Format Max Read Description Notes
Elements Write
2 4 CANA_BCD_CODED 6 R FirmWare
2 5 CANA_FLOAT 34 RW Keycode
2 6 CANA_FLOAT 6 R Sensor Reading
2 7 CANA_FLOAT 3 RW Security
2 8 CANA_BYTE 84 RW Time Schedule
2 9 CANA_BYTE 2 R Switched Output
2 10 CANA_PERCENT 6 R Analog Outputs
2 11 CANA_BYTE 19 RW Alarm Status
2 12 CANA_BYTE 1 R Control Status
2 13 CANA_BCD_CODED 7 RW Time
2 14 CANA_BYTE 4 R Staged Output Status
2 15 CANA_BYTE 1 RW Plant Status
4 4 CANA_BCD_CODED 6 R FirmWare
4 5 CANA_FLOAT 34 RW Keycode
4 6 CANA_FLOAT 6 R Sensor Reading
4 7 CANA_FLOAT 3 RW Security
4 8 CANA_BYTE 1 R Switched Output
4 9 CANA_PERCENT 5 R Analog Outputs
4 10 CANA_BYTE 16 RW Alarm Status
4 11 CANA_BYTE 1 R Control Status
4 12 CANA_BYTE 4 R Staged Output Status
4 13 CANA_BYTE 1 RW Plant Status
5 4 CANA_BCD_CODED 6 R FirmWare
5 5 CANA_SWAP_INT 100 RW Keycode
5 6 CANA_BYTE 4 R Sensor Reading
5 7 CANA_SWAP_INT 3 RW Security
5 8 CANA_BYTE 84 RW Time Schedule
5 9 CANA_BYTE 3 R Switched Output