FieldServer FS-8700-59 Computer Drive User Manual


 
FS -8700-59 Canatal Sachnet Driver Manual
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page
4
4.2 Client Side Connections
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the FieldServer
FS x40: P1-P8, R1-R2
FS x20: P1-R2
Baud Specify baud rate 1200
Parity Specify parity Even
Data_Bits Specify data bits 7
Stop_Bits* Specify stop bits 1
Protocol Specify protocol used Canatal, Satchnet
Handshaking* Specify hardware handshaking RTS, RTS/CTS, None
Poll Delay* Time between internal polls 0-32000 seconds
default 1 second
Example
// Client Side Connections
Connections
Port, Baud, Parity, Protocol, Data_bits, Stop_bits,
R1, 1200, Even, Canatal, 7, 1,
4.3 Client Side Nodes
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID Address of physical server node
(Canatal device address)
1-63
Protocol Specify protocol used Canatal, Satchnet
Port Specify which port the device is
connected to the FieldServer
FS x40: P1-P8, R1-R2
FS x20: P1-R2
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID, Protocol, Port
Conditioner1, 1, Canatal , R1