5. Configuring the FieldServer as a McQuay Micro Tech Open Protocol Server
5.1. Server Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
3
Baud* Specify baud rate
300, 1200, 2400, 4800 and 9600
baud (Vendor limitation)
Parity* Specify parity Even (Vendor limitation)
Data_Bits*
Specify data bits 7 (Vendor limitation)
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used MCQ, McQuay
Handshaking* Specify hardware handshaking
None
Example
// Server Side Connections
Connections
Port ,Baud ,Parity ,Data_Bits ,Protocol ,Handshaking ,Poll_Delay
P1 ,9600 ,Even ,7 ,McQuay ,None ,0.100s
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction