5. Configuring the FieldServer as a GE-EGD Server
5.1. Server Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Adapter Adapter Name N1,N2
Protocol Specify protocol used GE_EGD
Example
Adapters
Adapter, Protocol
N1, GE_Egd
5.2. Server Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID This keyword is not required.
IP_Address
The IP address in dot format
of the EGD-Device.
Nnn.nnn.nnn.nnn
Where nnn is in the range 0-
255.
Protocol Specify protocol used GE_Egd
Adapter
Specify which adapter
connects to the network the
EGD-device is connected to.
N1, N2
Example
// Producer(Active Server) Side Nodes
Nodes
Node_name, IP_Address, Adapter, Protocol
node_A, 192.168.1.102, N1, ge_egd