FieldServer FS-8704-16 Computer Drive User Manual


 
FS-8704-16 Omron FINS Manual Page 8 of 37
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Example
// Client Side
Connections
Adapters
Adapter, Protocol, Udp_port_number
N1, Fins, 9600
1.08 Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
IP_Address Provide IP Address of PLC Eg. 192.168.1.105
Node_ID
Node number set at PLC
The node number should
correspond to the last byte of
the IP address. Eg. 105
corresponds to the example IP
address above.
1-126
Protocol Specify protocol used Fins, omn_fins or fins_udp
Adapter
Specify which port the device is
connected to the FieldServer
N1, N2
3
*Net_Number
Provide the network number of
PLC
1-255
Example
// Client Side Nodes
Nodes
Node_Name, IP_Address, Node_ID, Protocol, Adapter, Net_Number
PLC 1, 192.168.1.5, 1, Fins, N1, 1
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.