FieldServer FS-8704-16 Computer Drive User Manual


 
FS-8704-16 Omron FINS Manual Page 22 of 37
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Appendix A.2. PLC status to execute commands
PLC Type
Memory
Type
Command name
Run
Mode
Monitor
Mode
Program
Mode
Access
right
5
UM Read
Protection
6
DIP UM
Protection
7
MEMORY AREA
READ
OK OK OK OK OK OK
I/O Memory
MEMORY AREA
WRITE
OK OK OK OK OK OK
RUN OK OK OK Disabled OK OK Operating
Mode
Changes
STOP OK OK OK Disabled OK OK
CLOCK READ OK OK OK OK OK OK Time Data
Access
CLOCK WRITE OK OK OK Disabled OK OK
CPU UNIT
STATUS READ
OK OK OK OK OK OK
CS1/CJ1
Series
Status
Reading
CYCLE TIME
READ
OK OK Disabled OK OK OK
5
Access Right at Other Device: The Access right at other device column tells whether the CPU Unit can or cannot receive a command when another device has
the access right to the CPU Unit.
6
UM Read Protection: The UM read protection column tells whether the CPU Unit can or cannot receive the command when UM (user memory) is protected
from a Peripheral Device.
7
DIP Switch UM Protection: The DIP switch UM protection column tells whether the CPU Unit can or cannot receive a command when UM is write-protected
by turning ON pin 1 of the DIP switch on the CPU Unit’s front panel.