FieldServer FS-8704-16 Computer Drive User Manual


 
FS-8704-16 Omron FINS Manual Page 32 of 37
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
ELEMENT
NUMBER
CONTENTS DESCRIPTION
43 1/0 1:Message # 7 Present
44 1/0 1:Message # 6 Present
45 1/0 1:Message # 5 Present
46 1/0 1:Message # 4 Present
47 1/0 1:Message # 3 Present
48 1/0 1:Message # 2 Present
49 1/0 1:Message # 1 Present
50 1/0 1:Message # 0 Present
51 0-65535 Error Code
52-67 A-Z 16 Character Text
Appendix B.2. Driver stats
In addition to the standard FieldServer operating statistics the driver exposes certain
key stats in a Data Array if required. An upstream device can then monitor these
stats.
Add the following to your configuration file to activate these stats.
// Expose Driver Operating Stats.
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
fins-stats, UINT32, 200
Stat
Number
Stats Description
0 FINS_BAD_START
Number of Messages received with bad start
byte.
1 FINS_NET
Number of Messages received with bad or
unsupported Network Number.
2 FINS_STATION
Number of Messages received with bad or
unsupported Node Number.
3 FINS_UNIT
Number of Messages received with bad or
unsupported Unit Number.
4 FINS_MRC
Number of Messages received with bad or
unsupported Main Request Code
5 FINS_SRC
Number of Messages received with bad or
unsupported Sub Request Code
6 FINS_SID
Number of Messages received with wrong or
Sequence Id.