FieldServer FS-X20 Server User Manual


 
Start-up guide
Page 2 FS-X20 Series FieldServer Start-up Guide (07-2005)
1. Pre-Installation Check List
1.1. Supplied equipment
The following components are supplied:
FS-X20 Series FieldServer, loaded with
Modbus RTU driver, SMT Ethernet
driver and any other drivers ordered.
1
FS-X20 Series Start-up Guide (T17005)
FieldServer Configuration Manual
(T17003)
FieldServer Utilities Manual (T17009)
Driver Manual(s) specific to all Drivers
ordered with the FieldServer.
Utility CD – note that the Utilities support
the following platforms only:
Windows XP
Windows 2000
Windows NT
Windows 98
Any additional Diskettes related to
special files configured for a specific
FieldServer.
Additional components as required -.
See Driver Manual Supplement for
details
An accessory bag consisting of the
following: :
DB9F/RJ45 Connection Adapter.
(Part Number FS-8917-02)
7-ft Cat5 cable with RJ45
connectors at both ends (Part
Number FS-8915-10)
RS-232 Mini Tester, 25-pin (Part
Number FS-8915-13)
RS-485 connector (Part Number
FS-SPA59137)
Set of four different connectors
DB9M, DB9F, DB25M, DB25F (Part
Number FS-8915-11)
Power Supply
Connector for power (SPA59136)
1.2. Start-up
Read this Start-up Guide in conjunction
with the Configuration Manual, the
1
Note that a default configuration file has
already been loaded onto the FieldServer.
Check the Driver Manual and the FieldServer
Configuration Manual for further information on
this file.
Driver Manual(s) and the Utilities
manual.
The power socket mates with a
pluggable terminal block, connector, that
is supplied separately (SPA59136). The
terminal block is manufactured by
Phoenix Contact, model MSTB, (PN
1754465), No.30-12 AWG, 5-7 in/lbs
torque.
USE COPPER CONDUCTORS ONLY
Select an external power supply certified
for safety, for the correct destination
country and an output rating, which is
considered a NEC Class 2 circuit or is a
SELV Limited power source with the
following ratings:
9-30 VDC, 1A; OR 24 VAC, 50/60Hz,
0.5A
INPUT VOLTAGE SPECIFICATION
24 VAC FLOATING
Using a grounded VAC will cause
irreparable damage to the product.
The operating environment for the
product is 0 to 60°C (32 to 140°F).