FieldServer FS-X20 Server User Manual


 
Start-up guide
Page 3 FS-X20 Series FieldServer Start-up Guide (07-2005)
2. Product Description
2.1. Specifications
Power requirements (power supply is external)
X20 power supply P/N 69155
Input voltage: 9-30VDC, 8W; 24VAC Floating. Voltage variation of ±10% tolerated.
Output voltage / current: 24VDC @ 0.5A
Physical Dimensions(excluding the external power supply)
(WxDxH): 3.82 x 4.08 x 1.7 inches (9.70 x 10.36 x 4.31 cm)
Weight: 0.8 lbs. (0.36 Kg)
Available Ports
1 x RJ45 / RS-232 serial connector
1 x RS-485 serial connector
1 x RJ45 10-BaseT Ethernet connector
Environment:
Operating Temperature: 0 – 60°C (32 – 140°F)
Humidity: 10 - 90% RH (non-condensing)
Approvals:
UL 916
ULC 916
FCC Tested to comply with FCC part 15
CE Marked
(Specifications subject to change without notice)
2.2. Mounting
The FS-X20 Series FieldServer is supplied
with an accessory bag which allows
selection of adhesive feet (for standing on a
shelf) or mounting plates for wall or panel
mount. A DIN Rail Mounting Kit (P/N FS-
8915-28) may be ordered separately.
2.3. Wiring
The 110VAC to 9VDC or 24VDC/ power
supply received with the unit needs to be
plugged into a power source and then
connected to the back of the FieldServer
using the SPA59136 connector. This power
supply is designed to temporarily provide the
9-24V 100mA required by the FieldServer
during testing and start-up. Permanent 9-
30V, 100mA power will need to be provided
for continuous operation.
The FS-X20 Series FieldServer is shipped
as either a FS-X20XX-01 in which case the
RS-232 port is activated, or as a FS-X20XX-
02 in which case the RS-485 port is
activated.
If using an RS-232 RJ45 Serial connection
then use one of the RJ45 cables to connect
from the appropriate port on the FieldServer
to the connection adapter provided with the
FieldServer or the Driver Kit. Then plug the
connection adapter to the node.
If using RS-485 from the node to the FS-
X2010, the + and - wire connections can be
used on the RS-485 port on the FieldServer.
For the FS-X2011, LonWorks
®
enabled
modules, the orange port is the TP/FT-10
connection, and the RS-485 connection
needs to be made via the serial RJ-45 port.
To change between RS-232 and RS-485
connection, it is necessary to modify
jumpers on the internal board. Refer to
eNote0017
2
for further information.
Ethernet connections simply require
connection of a standard Cat5 UTP Ethernet
cable with an RJ45 connector between the
FieldServer and the network. Note that
when connecting the FieldServer directly to
another Ethernet enabled device without
using a hub, then standard Ethernet
principles apply, and a Crossover cable
must be used.
Note that the USB port is not activated.
2
eNotes are available at
www.fieldserver.com/techsupport/enotes/enotes.asp