FieldServer IR-148 Computer Drive User Manual


 
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 12 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
5.3.2. Driver Specific Map Descriptor Parameters
Column Title Function Legal Values
Node_Name
Name of Node to which data
has to be sent.
One of the node names
specified in “Server Node
Descriptor” - section 5.2
Length Length of Map Descriptor
1-Maximum of Data Array
length.
Da_Byte_Array_Name*
Name of Data Array used to
lock the sensor. Driver will
report data for the locked
sensor only.
One of the Data Array
names from “Data Array”
section above
Data_Byte_Offset*
Specifies offset for
Da_Byte_Array_Name
Data array. This memory
location will be checked every
time if the user has locked a
sensor.
If this parameter is not
specified, the driver will use the
Data_Array_Offset value.
1-Maximum of Data Array
length.
Infra_Func
For quality assurance this
parameter is used to send a
message to a Client from a
Map_Descriptor_Name*.ini file.
With the use of this function
Data_Array_Offset value will be
used as line number from INI to
send.
INFRA_SIMULATION:
only
numbered line will be sent to
Client by the Map Descriptor.
INFRA_SIMULATION_ALL:
Starting at the numbered line all
lines will be sent one by one to
the Client until the end of the
file is reached.
INFRA_SIM_ALL_REPEAT:
Repeatedly Starting from
numbered line to end of the file
all lines will be sent to Client
one by one by this single Map
Descriptor.
Note: Ini must show all bytes as
two character hex
representation and first line of
should be
// FILE_IN_HEX_FORMAT
INFRA_SIMULATION
INFRA_SIMULATION_ALL
INFRA_SIM_ALL_REPEAT