FieldServer IR-148 Computer Drive User Manual


 
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 16 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
b) Extended storage : If the FieldServer is configured to use extended storage then data
will be stored as below
Offset Sensor
Contents Description
0 1 Alarm or Trouble
Non-zero if alarm or a trouble has been reported.
Zero if neither are currently being reported.
1 1 Alarm Type 0 = None, 1 = Caution, 2 = Warning, 3 = Alarm
2 1 Trouble 0=None, 1=Trouble
3 1 Gas Value
Gas value multiplied by 100 is stored here. When
stored, if configured, scaling will be applied.
4 1 Gas Units
5 1 Gas Units
6 1 Gas Units
1
st
3 bytes of gas units are written here as ASCII
characters.
7 1 State 0 = Enabled, 1 = Disabled
8 1 Gas Value Valid
1 = Gas Value updated with most recent message.
0 = Gas Value not updated.
9 1 Gas Value Age
In seconds since last update.
Initial (and max) value = 0xffff
10 1 Sensor Data Age
Age since last message, containing data from this
sensor in seconds. Initial (and max) value = 0xffff
11 1 I/O State
255 = unknown, 0=Warm up, 1 = Ready, 2 = Trouble,
3= Cal/Setup
12 1
Alarm Latched
Status
0=No, 1=Yes
13 1 Audion On Status 0=No, 1= Yes
14 1
Alarm Latching
Preference
On Caution (0=No, 1= Yes)
15 1
Alarm Latching
Preference
On Warning(0=No, 1= Yes)
16 1
Alarm Latching
Preference
On Alarm(0=No, 1= Yes)
17 1
Audio On
Preference
On Caution (0=No, 1= Yes)
18 1
Audio On
Preference
On Warning(0=No, 1= Yes)
19 1
Audio On
Preference
On Alarm(0=No, 1= Yes)
20 1
Audio On
Preference
On Trouble(0=No, 1= Yes)
21 1
Audio On
Preference
On Auxilary(0=No, 1= Yes)
22-24 1 Spare
25..49 2
50.-74 3
75.- 99 4
100-124 5
125..149 6
150.-174 7
175.-
199
8
The Driver expects similar a Data array format to send data to the Client when acting as a
Server.