FieldServer IR-148 Computer Drive User Manual


 
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 7 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8 (with 232/485 converter), R1-
R2
1
Protocol Specify protocol used InfraTox or Infra-Tox
Baud* Specify baud rate 19200 (Vendor limitation)
Parity* Specify parity
None (Vendor limitation)
Data_Bits* Specify data bits
8 (Vendor limitation)
Stop_Bits* Specify stop bits
1
Handshaking* Specify hardware handshaking
None (Vendor limitation)
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Stop_Bits
R1, InfraTox, 19200, None, 1
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID
Irrelevant for this driver as long
as only one Node is connected.
Otherwise the Node-ID should be
the number of points/sensors for
which the Zellweger unit is
configured. A unique Node_ID is
recommended for each Zellweger
Unit as it may be useful in
exposing Node status information
0-255
Protocol Specify protocol used InfraTox, Infra-Tox.
Port
Specify at which port the device is
connected to the FieldServer
Ports P1-P8 can be with 232/485
converter.
P1-P8 (with 232/485 converter),
R1-R2
1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.