FieldServer IR-148 Computer Drive User Manual


 
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 17 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
Appendix A.3. Driver stats
In addition to the standard FieldServer operating statistics the driver can expose certain key
stats in a Data Array which can then be monitored by an upstream device. Adding the
following to the configuration file will activate these stats for a driver configured as a Client.
// Expose Driver Operating Stats.
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
Infra-stats, UINT32, 200
Stat
#
Stats Description
0 INFRA_TROUBLE_MSG_RECV Number of trouble messages received
1 INFRA_TROUBLE_WITH_ALARM_MSG_RECV
Number of Alarm as well as Trouble
messages reported
2 INFRA_ALARM_MSG_RECV Number of Alarm messages reported
3 INFRA_GAS_VALUE_MSG_RECV
Number of Gas Value messages
reported
4 INFRA_GAS_VALUE_WITH_ALARM_MSG_RECV
Number of Gas value as well as Alarm
messages reported.
5 INFRA_LOCK_MSG_RECV Number of Lock messages reported
6 INFRA_BLANK_MSG_RECV Number of Blank messages reported
10 INFRA_ST_0xB1_49_RECV_DISC
Number of discarded messages
starting with 0xB1 with length 49 bytes
11 INFRA_BAD_ST_49_RECV_DISC
Number of discarded messages not
starting with 0xB1 with length 49 bytes
12 INFRA_NOT_49_RECV_DISC
Number of discarded messages with
length not 49 bytes.
13 INFRA_NOT_49_RECV_BYTES_DISC
Length of the latest discarded
message with length not 49 bytes.
20 INFRA_BAD_CRC_MSG_DISC
Number of messages discarded
because of bad checksum.
For the node connected at R1; Offset = Stat number
Example: The number of messages discarded because of bad start can be found at Offset 11
in Infra-Stats Data Array.
For the node connected at R2; Offset = 100 + Stat number
Example: The number of messages discarded because of bad start can be found at Offset
111 in Infra-Stats Data Array.