GD Systems
Page - 5 Windmill
Device Type The device type of the unit installed. To ensure correct operation this value must be correct.
The codes follow the product code. If you are unsure then the ‘X’ option must be used. Zone
The zone number must be programmed between the following values
EDA-M100 system 1 – 999 zones
EDA-M200 system 1-20 zones
Locations Text The device location text can be set using a maximum of 37 characters
Day/Night Mode On If analogue devices are being used (500 and 600 range of detectors) then for individ-
ual units the day night mode can be selected. In the global options the start and end time of this mode
can be selected and the sensitivity changed during these hours can be selected.
Sensitivity If analogue devices have been fitted *500 and 600 range of detectors) then the sensitivity can be
selected. The default is ‘Normal’ but if a higher sensitivity is required for computer rooms or high risk areas
the sensitivity should be set higher. If devices are fitted in hostile areas or roof voids then the lower
sensitivity should be set.
2nd Input Used If the 2nd input is being used this check box must be selected to allow a unit number to be
entered.
2nd Input Device Number If the 2nd input is used a device number must be assigned. This will be the de-
vice number displayed on the panel should the 2nd input detect an alarm condition. If not defined it will de-
fault to the next unit number provided the panel is put into the self learn mode. To ensure this operates
correctly the unit should always be assigned if being used.
Save and Exit To return to the previous screen this button must be pressed.
Once changes are made they are automatically saved and can only be changed back by re-typing the older
values.
5.4.2 Change Device Cause and Effects
If the cause and effects for a particular device need to be changed position the scroll bar to detail the ap-
propriate unit number and double click on the column labelled ‘Special’ for the particular device. Screen 5.4
will be displayed. The cause and effects are listed in the following section.
If the device number is not correct then the up and down arrows can be used to reposition the device
number. It should be noted that any changes made prior to changing the device number will automatically
be saved.