GD Systems
Page - 7 Windmill
Radio Sounders Tone The tone for the radio sounder can be set. The default tone is tone 4 (swept Tone). If
EDA-A910 hardwired sounders are being used to match the tone of the radio units then the tone for the
hardwired sounders is set inside the individual units. Radio Sounder Auxiliary If the radio sounders are fit-
ted with auxiliary outputs or output devices are fitted then this should be checked to operate the auxiliary
output.
Radio Sounders Area If the radio sounders have been grouped in to areas then the system can be pro-
grammed to sound individual areas. The default is to sound all areas. If a separate area is required to
sound, then the areas should be entered into the fields. A maximum of three areas can be programmed to
sound for a single alarm condition. Values should be entered from left to right and if not used left as 0.
Second Delay Once the first delay has expired the second delay will commence if set. After this delay has
expired the cause and effects will operate as detailed in the corresponding settings.
See the previous section for the values required.
Which Panel - This is not implemented yet.
Store as Default Store the values set on the screen to temporary memory, to enable them to be loaded
back for other units. This enables common changes to be made to multiple devices quickly and
easily.
Set to Default If the ‘Store as Default’ button was used earlier in the session then those saved values can
be loaded into the current selected unit number. Select the unit number and click the ‘Set to Default’ button.
5.5 Change Panel Settings
To change panel settings position the scroll bar to display the appropriate panel number and double click
anywhere on the line of the appropriate panel number. Panel numbers are always preceded by a ‘P’ on the
list of devices. A screen similar to figure 5.5 will be displayed.
For a description of the relays available see section 5.4.1
Location Text The location text details the position of the control or booster panel in the building. Its length
has a maximum of 37 characters
Evacuate - When Evacuate is pressed on the corresponding panel the sounder circuits, auxiliary relays and
radio sounders will operate as programmed. For a more detailed description of the sounder circuits, auxil-
iary relays and radio sounders see the device programming section (5.4.1)