HP (Hewlett-Packard) BL30p Network Card User Manual


 
EMI
EMIEMI
EMI
FCC Part 15 Class A
EN 55022: 1998 (CISPR22)
EN 55024: 1998 (CISPR24)
CNS 13438 Class A MIC
CD
MIC
AS/NZS 3548 Class A CE
VCCI Class A
Safety
SafetySafety
Safety
UL to UL 60950, Third Edition
C-UL to CAN/CSA C22.2 No. 60950-00, Third Edition
TUV/GS to EN 60950:2000
CB to IEC 60950 with all country deviations
NOM to NOM-019-SCFI
CE Marking
Power
PowerPower
Power
Requirements
RequirementsRequirements
Requirements
-48VDC: 1050 mA, 125 W maximum (per interconnect switch)
Temperature Range
Temperature RangeTemperature Range
Temperature Range
Operating
50 to 95º F (10 to 35º C)
Non-operating
-22 to 140º F (-30 to 60º C)
Relative Humidity
Relative HumidityRelative Humidity
Relative Humidity
(non-condensing)
Operating
20% to 85%
Non-operating
5% to 95%
Wet Bulb
Wet BulbWet Bulb
Wet Bulb
Temperature
TemperatureTemperature
Temperature
Operating
82.4° F (28° C)
Non-operating
101.7° F (38.7° C)
NOTE:
NOTE: NOTE:
NOTE:
Operating temperature has an altitude derating of 34° F (1° C) per 1,000 ft (304.8 m). No
direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating
limit is 30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a
maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.
Operating and
Operating andOperating and
Operating and
Performance
PerformancePerformance
Performance
Specifications for 3U HP
Specifications for 3U HPSpecifications for 3U HP
Specifications for 3U HP
BladeSystem
BladeSystemBladeSystem
BladeSystem
p-Class Power Enclosures
p-Class Power Enclosuresp-Class Power Enclosures
p-Class Power Enclosures
(North America/Japan)
Single-Phase Model
Single-Phase ModelSingle-Phase Model
Single-Phase Model
3-Phase Model
3-Phase Model3-Phase Model
3-Phase Model
Dimensions
DimensionsDimensions
Dimensions
Height
5.25 in (13.34 cm) 5.25 in (13.34 cm)
Width
27.15 in (68.96 cm) 27.15 in (68.96 cm)
Depth
17.60 in (44.7 cm) 17.60 in (44.7 cm)
Weights
WeightsWeights
Weights
No Hot-Plug
Power Supplies
47.5 lb (21.55 kg) 47.5 lb (21.55 kg)
All Hot-Plug
Power Supplies
99.5 lb (45.13 kg)
125.5 lb (56.93 kg)
Input Requirements
Input RequirementsInput Requirements
Input Requirements
Rated input voltage
200 VAC to 240 VAC 200 VAC to 240 VAC
line to line
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current
per side
24A
24A per phase
Rated input power
per side
5760 W 9976 W
Power cord
1 NEMA L6-30P per
side
1 NEMA L15-30 per
side
QuickSpecs
HP ProLiant BL30p Server Blade
HP ProLiant BL30p Server BladeHP ProLiant BL30p Server Blade
HP ProLiant BL30p Server Blade
Technical Specifications
DA - 11958 Worldwide — Version 19 — August 15, 2005
Page 44