HP (Hewlett-Packard) BL30p Network Card User Manual


 
Output Voltage
Output VoltageOutput Voltage
Output Voltage
Specifications
SpecificationsSpecifications
Specifications
Rated output voltage
-48.8 VDC to -54 VDC -48.8 VDC to -54 VDC
Rated output current
99A
170A
Rated output power
4298 W 8310 W
Nominal power
4158 W at 208 VAC 7202 W at 208 VAC
Ambient Temperature
Ambient TemperatureAmbient Temperature
Ambient Temperature
Range
RangeRange
Range
(See
NOTE
NOTENOTE
NOTE
)
Operating
50° to 95° F
(10° to 35° C)
50° to 95° F
(10° to 35° C)
Shipping
-22° to 140° F
(-30° to 60° C)
-22° to 140° F
(-30° to 60° C)
Relative humidity,
Relative humidity,Relative humidity,
Relative humidity,
non-condensing
non-condensingnon-condensing
non-condensing
(See
NOTE
NOTENOTE
NOTE
)
Operating
20% to 80% 20% to 80%
Non-operating
5% to 95% 5% to 95%
Wet Bulb
Wet BulbWet Bulb
Wet Bulb
Temperature
TemperatureTemperature
Temperature
Operating
82.4° F (28° C) 82.4° F (28° C)
Non-operating
101.7° F (38.7° C) 101.7° F (38.7° C)
NOTE:
NOTE: NOTE:
NOTE:
Operating temperature has an altitude derating of 34° F (1° C) per 1,000 ft (304.8 m). No
direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating
limit is 30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a
maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.
Operating and
Operating andOperating and
Operating and
Performance
PerformancePerformance
Performance
Specifications for 3U HP
Specifications for 3U HPSpecifications for 3U HP
Specifications for 3U HP
BladeSystem
BladeSystemBladeSystem
BladeSystem
p-Class Power Enclosures
p-Class Power Enclosuresp-Class Power Enclosures
p-Class Power Enclosures
(International)
Single-Phase Model
Single-Phase ModelSingle-Phase Model
Single-Phase Model
3-Phase Model
3-Phase Model3-Phase Model
3-Phase Model
Dimensions
DimensionsDimensions
Dimensions
Height
5.25 in (13.34 cm) 5.25 in (13.34 cm)
Width
27.15 in (68.96 cm) 27.15 in (68.96 cm)
Depth
17.60 in (44.7 cm) 17.60 in (44.7 cm)
Weights
WeightsWeights
Weights
No Hot-Plug
Power Supplies
47.5 lb (21.55 kg) 47.5 lb (21.55 kg)
All Hot-Plug
Power Supplies
99.5 lb (45.13 kg)
125.5 lb (56.93 kg)
Input Requirements
Input RequirementsInput Requirements
Input Requirements
Rated input voltage
200 VAC to 240 VAC
6.25 A at -48 VDC
200 VAC to 240 VAC
line to neutral
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current
per side
24A
20A per phase
Rated input power
per side
5760 W
10,552 W
Power cord
1 IEC 309 3-pin,
32A per side
1 IEC 309 5-pin,
32A per side
Output Voltage
Output VoltageOutput Voltage
Output Voltage
Specifications
SpecificationsSpecifications
Specifications
Rated output voltage
-48.8 VDC to -54 VDC -48.8 VDC to -54 VDC
Rated output current
99A
180A
Rated output power
4798 W 8790 W
Nominal power
4598 W at 208 VAC
8790 W at 230 VAC L-
N
Ambient Temperature
Ambient TemperatureAmbient Temperature
Ambient Temperature
Range
RangeRange
Range
(See
NOTE
NOTENOTE
NOTE
)
Operating
50° to 95° F
(10° to 35° C)
50° to 95° F
(10° to 35° C)
Shipping
-22° to 140° F
(-30° to 60° C)
-22° to 140° F
(-30° to 60° C)