HP (Hewlett-Packard) GS1280 Computer Hardware User Manual


 
GS1280 Model 8
1 I/O Drawer, 1 SW
Shelf
GS1280 Model 16
1 I/O Drawer, 1 SW
Shelf
GS1280 Model 32
1 I/O Drawer, 1 SW
Shelf
GS1280 Model 64
1 I/O Drawer, 1 SW
Shelf
Power Required, Kva
3.5 5.7
10.1 18.7
Power Distribution Unit
(PDU) required for all
GS1280 Models 3X-H7606-
Ax
1 required; 2 for dual
AC
2 required; 4 for dual
AC
2 required, dual AC
included
2 required, dual AC
included
Power Distribution Unit
(PDU) required for GS 1280
Models 32 and 64, 3X-
H7606-Bx
Not applicable Not applicable
2 required, dual AC
included
4 required, dual AC
included
Physical Characteristics
Dimensions (H x W x D)
79 x 24 x 47 in (200 x 60 120 cm) (one 41U Rack)
Shipping Dimensions
86 x 32 x 48 in (217 x 92.5 142 cm) (one 41U Rack)
GS1280 Model 8
GS1280 Model 16 GS1280 Model 32 GS1280 Model 64
Installed Weight, base system
870 lb (395 kg)
1,272 lb (577 kg)
2,118 lbs (961 kg)
4,800 lbs (2,176 kg)
Heat dissipation
Max Heat Output, Base Model
only, watts
3,405 6,810
14,820 28,440
Max heat Output, Base Model
only, Btu/hr
11,622 23,243 50,581 97,066
Typical Heat Output, Base
Model only, watts
2,430 3,700 8,000
14,800
Typical Heat Output, Base
Model only, Btu/hr
8,297
12,632 27,304 50,513
Airflow, cfm, minimum full
rack, each CPU rack
912
1,562 1,800
1,800 x 2 racks
Airflow, cfm, maximum full
rack, each CPU rack
1,404 2,454 3,400
3,400 x 2 racks
Airflow, cfm, minimum full
rack, power rack for Model 32
and 64
1,324 1,455
Airflow, cfm, maximum full
rack, power rack for Model 32
and 64
1,508 1,685
QuickSpecs
HP AlphaServer GS1280 Systems
Technical Specifications
DA - 11921 Worldwide — Version 24 — July 23, 2007
Page 58