HP (Hewlett-Packard) R12000 XR Power Supply User Manual


 
LCD Configuration and Status
Displaying the Status or Active Alarms
The first option on the Main Menu is Status. Select this option and press the Enter button to
display the status or active alarms for either the main module or electronics modules M1-M4.
Main Menu
Status
Main Module (MM) Status and Alarms
Select Main Module MM to display Status and Alarms for the main module. Table 3-3 lists
the possible status options. For a descriptive list of alarm causes and solutions, refer to the
section, “LCD Alarm Troubleshooting,” in Chapter 5.
Status: Select
Main Module MM
NOTE: A display of x Alarms means that one or more alarms are present. The variable x indicates the
number of alarms.
Table 3-3: Main Module Status Options
LCD Display Explanation
Load Power Off The UPS is in Standby mode and is not supporting the load.
System Normal
0 Alarms
The UPS is operating normally from utility and is protecting the load.
No alarms are present.
Load Power On
x Alarms
The UPS is operating from utility and is protecting the load.
On Battery
x Alarms
The UPS is operating from battery and is protecting the load.
On Bypass
x Alarms
The UPS is operating from Automatic Bypass mode and is not
protecting the load.
Manual Bypass
x Alarms
The UPS is operating from Manual Bypass mode and is not
protecting the load.
Overload
x Alarms
The UPS is protecting the load. The current load level is exceeding
the maximum operational range for the UPS.
Autocalibrating
x Alarms
The UPS is operating from utility and is protecting the load while it is
performing the module-sharing calibration process.
continued
HP Uninterruptible Power System R12000 XR Models User Guide 3-7
HP CONFIDENTIAL Codename: Sierra Part Number: 146316-002 Last Saved On: 1/24/03 10:15 AM