HP (Hewlett-Packard) R12000 XR Power Supply User Manual


 
LCD Configuration and Status
Choose the baud rate for the selected serial port or option slot.
Table 3-9: Baud Rate Setup
LCD Display Explanation
Baud Rate
x
Choose the baud rate for the serial port or option slot selected
above. Here, x is the baud rate and can be equal to 1200, 2400,
4800, 9600 (default) or 19200.
An asterisk (*) indicates the current baud rate.
Setting the Voltage
Select Set Voltage from the System Setup menu to set the voltage. The asterisk (*) indicates
the current configuration. The options for voltage are 200, 208, 220, 230 (default), and 240.
System Setup
Set Voltage
NOTE: This option is only available when the UPS is in Standby mode or Manual Bypass mode.
Otherwise, the LCD panel indicates Not Available.
Setting the Hardware Configuration
Select Set HW Config from the System Setup menu to set the hardware configuration for the
UPS.
System Setup
Set HW Config
Table 3-10: Hardware Configuration Choices
LCD Display Explanation
Set HW Config
ERM Setup
Select this option to configure the number of ERMs
installed.
Set HW Config
Commission Battery
Select this option to enable a battery commissioning test.
Set HW Config
Parallel Mode
Select this option to go to the Parallel Mode menu options.
HP Uninterruptible Power System R12000 XR Models User Guide 3-13
HP CONFIDENTIAL Codename: Sierra Part Number: 146316-002 Last Saved On: 1/24/03 10:15 AM