HP (Hewlett-Packard) sx2000 Computer Hardware User Manual


 
Grounding
The site building must provide a safety ground or protective earth for each ac service entrance
to all cabinets.
WARNING! This equipment is Class 1 and requires full implementation of the grounding
scheme to all equipment connections. Failure to attach to protective earth results in loss of
regulatory compliance and creates a possible safety hazard.
Circuit Breaker
Each cabinet using a 3-phase, 4-wire input requires a dedicated circuit breaker to support the
Marked Electrical current of 44 A per phase. The facility electrician and local service codes
determine proper circuit breaker selection.
Each cabinet using a 3-phase, 5-wire input requires a dedicated circuit breaker to support the
Marked Electrical current of 24 A per phase. The facility electrician and local service codes
determine proper circuit breaker selection.
NOTE: When using the minimum-size breaker, always choose circuit breakers with the
maximum allowed trip delay to avoid nuisance tripping.
Power Options
Table 2-6 describes the available power options. Table 2-7 provides details about the available
options. The options listed are consistent with options for earlier Superdome systems.
Table 2-6 Available Power Options
Power Receptacle RequiredInput Current Per
Phase 200 to 240 V
ac
1
PDCA
Required
Source Voltage
(Nominal)
Source
Type
Option
Connector and plug provided
with a 2.5 meter (8.2 feet) power
cable. Electrician must hardwire
the receptacle to 60 A site power.
44 A maximum per
phase
4-wireVoltage range 200 to 240
V ac, phase-to-phase, 50
Hz/60 Hz
3-phase6
Connector and plug provided
with a 2.5 meter (8.2 feet) power
cable. Electrician must hardwire
the receptacle to 32 A site power.
24 A maximum per
phase
5-wireVoltage range 200 to 240
V ac, phase-to-neutral,
50 Hz/60 Hz
3-phase7
1 A dedicated branch circuit is required for each PDCA installed.
Table 2-7 Option 6 and 7 Specifics
Receptacle RequiredAttached PlugAttached Power CordPDCA Part
Number
Mennekes ME
460R9 (60 A
capacity)
Mennekes ME
460P9 (60 A
capacity)
OLFLEX 190 (PN 600804) is a 2.5 meter (8.2 feet)
multiconductor, 600 V, 90˚ C, UL and CSA approved,
oil resistant flexible cable (8 AWG 60 A capacity).
A5201-69023
(Option 6)
Mennekes ME
532R6-1500 (32 A
capacity)
Mennekes ME
532P6-14 (32 A
capacity)
H07RN-F (OLFLEX PN 1600130) is a 2.5 meter (8.2 feet)
heavy-duty neoprene-jacketed harmonized European
flexible cable (4 mm
2
32 A capacity).
A5201-69024
(Option 7)
Electrical Specifications 51