HP (Hewlett-Packard) XP1024 Network Router User Manual


 
44 HP StorageWorks Disk Arrays XP128/XP1024: Owner’s Guide
AC line voltage
The following AC power recommendations for the HP StorageWorks Disk
Array XP128 are for each power cord. Each array frame has two power
cords (with the AC power cord option there are four cords). In case of a
failure of the power source for one cord, the power requirements and the
current requirement for the remaining power cord will double.
Table 6 (page 44) lists the basic AC power requirements for a 50-amp
single-phase XP128 DKU. Table 7 (page 44) lists the basic AC power
requirements for a 30-amp single-phase XP128 DKU.
Table 6. 50-Amp, 50 or 60 Hz, Single-Phase DKU Operation
Table 7. 30-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Nominal Rated Voltage (Vac)
200 208* 220 230 240
Rated line current per
power cord (Arms)
16.2 15.1 14.9 14.3 13.8
Number of power cords22222
Number of circuit breakers22222
Recommended circuit
breakers
50A 50A 50A 50A 50A
* 60 Hz only.
Parameter
Nominal Rated Voltage (Vac)
200 208* 220 230 240
Rated line current per
power cord (Arms)
10.2 9.5 9.4 9.0 8.7
Number of power cords 4 4 4 4 4
Number of circuit breakers 4 4 4 4 4
Recommended circuit
breakers
30A 30A 30A 30A 30A
* 60 Hz only.