HP (Hewlett-Packard) XP1024 Network Router User Manual


 
76 HP StorageWorks Disk Arrays XP128/XP1024: Owner’s Guide
Table 20 (page 76) lists the basic AC power requirements for a 60-amp,
three-phase XP1024 R1 DKU.
Table 21 (page 76) lists the basic AC power requirements for 60-amp,
three-phase, R2, L1, and L2 XP1024 DKUs. Unlike the first DKU (R1),
DKUs R2, L1, and L2 do not provide AC power to the DKC.
Table 20. 60-Amp, 50 or 60 Hz, three-phase R1 DKU operation
Parameter
Nominal Rated Voltage (Vac)
200 208
1
220 230 240 380 400 415
Rated line current per
power cord (Arms)
19.0 18.2 17.2 16.6 15.7 10.7 10.2 9.8
Number of power
cords
22222222
Number of circuit
breakers
22222222
Recommended circuit
breakers
60 A60 A60 A60 A60 A30 A
min
2
30 A
min
2
30 A
min
2
1. 60 Hz only.
2. 30-amp breakers are adequate at 380, 400, and 415 Vac, because the current
drawn at these voltages is considerably less than at the lower voltages.
Table 21. 60-Amp, 50 or 60 Hz, three-phase, R2, L1, and L2 DKU operation
Parameter
Nominal Rated Voltage (Vac)
200 208
1
220 230 240 380 400 415
Rated line current per
power cord (Arms)
19.0 18.2 17.2 16.6 15.7 10.7 10.2 9.8
Number of power
cords
22222222
Number of circuit
breakers
22222222
Recommended circuit
breakers
60 A60 A60 A60 A60 A30 A
min
2
30 A
min
2
30 A
min
2
1. 60 Hz only.
2. 30-amp breakers are adequate at 380, 400, and 415 Vac, because the current
drawn at these voltages is considerably less than at the lower voltages.