AC line voltage requirements for the HP Disk Array XP1024 (DKC)
Table 15 (page 73) lists the basic AC power requirements for a 40-amp,
single-phase XP1024 DKC.
Table 16 (page 73) lists the basic AC power requirements for a 30-amp,
single-phase, XP1024 DKC.
Table 15. 40-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Nominal Rated Voltage (Vac)
200 208* 220 230 240
Rated line current per power cord
(Arms)
8.0 7.7 7.2 7.0 6.6
Number of power cords 2 2 2 2 2
Number of circuit breakers 2 2 2 2 2
Recommended circuit breakers 40 A 40A 40A 40A 40A
* 60 Hz only.
Table 16. 30-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Nominal Rated Voltage (Vac)
200 208* 220 230 240
Rated line current per power cord
(Arms)
4.0 3.9 3.6 3.5 3.3
Number of power cords 4 4 4 4 4
Number of circuit breakers 4 4 4 4 4
Recommended circuit breakers 30 A 30 A 30 A 30 A 30 A