HP (Hewlett-Packard) XP1024 Network Router User Manual


 
72 HP StorageWorks Disk Arrays XP128/XP1024: Owner’s Guide
Specifications
Some of the XP1024 disk array specifications are listed in this section.
Refer to the HP Disk Array XP1024 Site Prep Guide on the XP1024 web
site at on the following main web site and access the appropriate product
for a complete set of XP1024 specifications:
http://www.hp.com
Temperature
Table 12. Temperature Specifications
Temperature Specifications (Degrees F = 1.8 x Degrees C + 32)
Nonoperating/storage Temperature Range
–10
° to +43° C
Operating Temperature
+16
° to + 32° C
Recommended Operating Temperature Range
+21
° to +24° C
Shipping and storage temperature
–25
° to 60° C
Temperature Shock Immunity—Maximum rate of
change
10
° C per hour
Over-Temperature shutdown
Shutdown at 60
° C
Table 13. Humidity Specifications
Humidity Specifications
Nonoperating/storage Humidity Range 5% to 95 % RH
Non-operating humidity range 8% to 90%
Operating Humidity Range at 22
° C
20% to 80 % RH
Recommended Operating Humidity Range at 22
° C
50% to 55 % RH
Procedure for recovery from moisture condensation None
Table 14. Mechanical Vibration Specification
Mechanical Vibration Specifications
Maximum Operating
Acceleration
0.05 G at a frequency range of 10 to 300 Hz