Hitachi SJ2-CO Power Supply User Manual


 
CHAPTER4 SETTING
9
4.1 Setting methods of Baud rate and Node ID
Follow the procedure below to set Baud rate in CANopen and Node ID, reset the power supply after
changing the setting (setting will be reflected after resetting power supply.). Initial Baud rate: 125kbps,
Initial Node ID: 2.
4.1.1 Setting method of CANopen Baud rate
The table below is setting method of Baud rate with Dip switch.
Baud rate
(kbps)
Dip switch
Setting
Note
Baud rate
(kbps)
Dip switch
Setting
Note
10 250
25 500
50
For bus
length
greater than
1km bridge
or repeater
device may
be needed
.
800
125 1000
4.1.2 Setting method of CANopen Node
Figure left describes the direction of Dip Switches. See below
ON: 1  OFF: 0
Bit increases from right to left switches. Figure formula below.
NODE ID = NA64*2
6
+ NA32*2
5
+ NA16*2
4
+ NA08*2
3
+ NA04*2
2
+ NA02*2
1
+ NA01*2
0
NA64 NA16NA32 NA08 NA04 NA02 NA01
DR
NODE ID
ON
OFF
1-9 = OFF, 10=ON:
NODE ID = 1