Hitachi CP-X200 Power Supply User Manual


 
Potentiometer Settings
Input Range Settings The parameters in the following table adjust the input
characteristics of the integrated potentiometer. When using the potentiometer to
command the inverter output frequency, these parameters adjust the starting and
ending ranges for the potentiometer, as well as the output frequency range.
“A” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Pot. input active range start
frequency
A151
POT-EXS 0000.0Hz
The output frequency
corresponding to the pot. range
starting point,
range is 0.0 to 400.0 Hz
U
0.0 0.0 Hz
Pot. input active range end
frequency
A152
POT-EXE 0000.0Hz
The output frequency
corresponding to the pot. range
ending point,
range is 0.0 to 400.0 Hz
U
0.0 0.0 Hz
Pot. input active range startA153
POT-EX%S 00000%
The starting point (offset) for the
potentiometer range,
range is 0. to 100.%
U
0. 0. %
Pot. input active range endA154
POT-EX%E 00000%
The ending point (offset) for the
potentiometer range,
range is 0. to 100.%
U
100. 100. %
Pot. input start frequency
enable
A155
POT-LVL 0Hz
Two options; select codes:
00}Use offset (A151 value)
01}Use 0Hz
U
01 01
Max frequency
A152
A151
A
154
100%
Counterclockwise
Clockwise
A
153
0%
A015=00
A015=01
0
Input scale
%
331
Configuring Drive
Parameters
3 31
&RQ¿JXULQJ'ULYH
Parameters