Honeywell HCE 60 Network Card User Manual


 
Creating a zoning plan
6
For more than 8 temperature zones or 24 actuators:
Determine the number of additional storey controllers required using
the following table:
Temperature
zones (maximum)
Actuators
(maximum)
No. of
storey controllers
824 1
16 48 2
24 72 3
The example at the end of this section shows zone divisions
with corresponding zoning plan.
Filling out zoning plan
Copy the sample zoning plan (see Appendix, Page 50) (archive it).
Enter the type and installation location of the respective actuator in
each temperature zone.
Assign a setpoint adjuster to each temperature zone.
Assign room names if necessary.
Hand over the zoning plan to the customer after installation.