IBM 4SA Personal Computer User Manual


 
154 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA
22.0-950, EN-60950, and IEC-950 standards. The following table contains the product
specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 1.5 kg (3.2 lbs)
Operating temperatures 10°C35°C (50°F95°F) at 0914 m (03000 ft)
10°C32 °C (50°F90°F°) at 9142133 m (30007000 ft)
Operating humidity 880% (non-condensing)
Rated voltage 100240 V ac, 15 A, single-phase
Rated frequency 5060 Hz
Maximum power rating 3600 VA
Circuit breaker Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.
Power inlet IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Power outlets Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)