I-Data POLARIS Panel PC 19.1" Personal Computer User Manual


 
User manual
POLARIS Panel PC 19.1'' and Panel PC 15''
Version 2.00 Page 23 of 46
E_BMS790_POLARIS_PanelPC_19+15_Rev1.doc User manual for POLARIS Panel PC 19.1" and 15" Revision 1 / Status: January, 3
rd
, 2006 Technical data subject to change
5.3 Installation options
The POLARIS Panel PC can be installed directly in
Switch cabinet doors
Mimic panels
Enclosures
In order to guarantee IP 65, use the reinforcement frame and the enclosure’s own IP rating has to be suitable for the
application.
The following points should be taken into consideration when installing the POLARIS Panel PC:
Convenient height for operation.
Good lighting so that the display will be easily readable.
At ambient temperatures below 0°C, the POLARIS Panel PC has to be heated.
Below +10°C the POLARIS Panel PC needs to be heated to maintain
the lifetime of the backlight illumination.
Avoid installing in the immediate vicinity of switching devices or converters.
Note: Only use heating systems, which are certified for explosive areas!
The following factors should be taken into consideration in order to ensure proper and workmanlike installation:
The installation location must be sufficiently stable / fixed.
The enclosure in which the POLARIS Panel PC is mounted must be strong enough to support
its weight.
Following the cutting out of the opening into which the POLARIS Panel PC is to be fitted, the
surface must be dressed to ensure it is smooth, level and undamaged so as to preserve the
integrity of the seal.
5.3.1 Cable glands / Conduits
When connecting cables and leads to supplies / communications equipment in increased safety protected areas, Ex certified
cable entries must be used which are suitable for each type of cable and lead. You must maintain the protection concept “e”
and include a suitable sealing element so that an IP rating of at least IP 54 is maintained.