Lathem PC3500TX Time Clock User Manual


 
16 - PC3500TX Terminal Installation & User’s Guide
If the terminal accepts the badge, the badge number displays and the terminal beeps.
To continue in the TEST MODE, press the CLEAR key three (3) times. You will then
see Battery Test.
Battery Test
If you purchased the optional battery (UPS), you can use the Battery Test to check the
battery. To start this test, press Enter when you see “BATTERY TEST”. You will then
see.
BATTERY TEST PASS
ENTER TO RETEST
Note: If you do not have a battery installed, the test will fail.
Press Clear to go to the DI-DO Test.
DI-DO Test
If you have installed a bell relay, you can use the DI-DO Test to check the terminal’s
DATA IN/DATA OUT port where the relay connects to the terminal.
To start the DI-DO Test
Press Enter when you see “DI-DO TEST”. You will then see
SWITCH TEST SWITCH
TO USE POSITION
Place the Test switch into the USE position. Since your terminal does not have a
loop back jumper, you will see
DI-DO TEST FAILED
ENTER TO RETEST
Place the Test/Use switch back into the TEST position. This provides the terminal
with its own loop back jumper
Press Enter. You will see
DI-DO TEST PASSED
ENTER TO RETEST
Press Clear to go to Restart Mode