Liebert 600T Power Supply User Manual


 
1
IMPORTANT SAFETY INSTRUCTIONS
Save These Instructions.
This manual contains important instructions that should be followed during installation of your
Series 600T UPS and batteries.
WARNING
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS
TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL.
THE UPS MODULE WEIGHT RANGES UP TO 12,000 POUNDS
(5,455 KG), INCLUDING INPUT TRANSFORMER. THE BATTERY
CABINETS WEIGH BETWEEN 3000 POUNDS (1364 KG) AND 4900
POUNDS (2227 KG).
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING
EACH CABINET. TEST LIFT AND BALANCE THE CABINETS
BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM
VERTICAL AT ALL TIMES.
SLOTS AT THE BASE OF THE MODULES AND BATTERY
CABINETS ARE INTENDED FOR FORKLIFT USE. BASE SLOTS
WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE
COMPLETELY BENEATH THE UNIT.
SYSTEM CONTROL CABINETS (SCC’S) HAVE HOLES
INTENDED FOR RIGGING BARS OR CHAINS. PREVENT
CHAINS OR CABLES FROM CONTACTING CABINET BY USING
SPREADER BAR AND ADEQUATE PADDING.
FOLLOW ALL BATTERY SAFETY PRECAUTIONS WHEN
INSTALLING, CHARGING, OR SERVICING BATTERIES. IN
ADDITION TO THE HAZARD OF ELECTRIC SHOCK, GAS
PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND
SULFURIC ACID CAN CAUSE SEVERE BURNS.
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT,
ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE
APPROVED FOR USE IN ELECTRICAL FIRE FIGHTING,
SHOULD BE USED.
EXTREME CAUTION IS REQUIRED WHEN PERFORMING
MAINTENANCE.
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS
HIGH DC AS WELL AS AC VOLTAGES.
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS
PRIOR TO MAKING CONTACT.