Liebert ITR Network Card User Manual


 
Split System Models
53
7.6 Water and Glycol-Cooled Condensing Units
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 48.
7.6.1 Piping Considerations
It is recommended that manual service shut-off valves be installed at the supply and return line to
each unit. This will provide for routine service or emergency isolation of the unit.
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil-
ters in the supply line. These filters will trap the particles in the water supply and extend the service
life of the water-cooled condenser.
7.6.2 Condenser Water Requirements
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure,
consult the factory about high pressure systems.
The system will operate in conjunction with a cooling tower, city water, or drycooler.
7.6.3 Regulating Valve Adjustment and Testing
Refer to 4.3.1 - Water Regulating Valve Adjustment and 4.3.3 - Testing Valve Function.
7.6.4 Glycol Systems
For split system glycol systems, use drycooler and pump data found in 5.0 - Glycol/GLYCOOL-
Cooled Models. See Table 16 - Drycooler data.
Electrical control interconnect to drycooler is wired from water/glycol condensing unit.
Table 30 Water and glycol-cooled unit connection sizes
Connection Size and Type
Condenser Water Inlet 1-1/8" OD Cu
Condenser Water Outlet 1-1/8" OD Cu
Suction Line 1-7/16" - 16 male #12 quick connect
Liquid Line 1-1/16" - 12 male #10 quick connect
Table 31 Water and glycol-cooled condensing unit data
Model
Net Weight Glycol Volume
lb kg gal liters
MC_69W
MC_68W
282 128 2.0 7.6