Liebert UPS Power Supply User Manual


 
10
GXT6000T / 10000T - 208 UPS ONLY
Models whose part number ends with a “208” are NOT fitted with an isolating
output transformer and are NOT separately derived sources under the NEC. The
output L1 terminal is connected to the input L1 terminal and must not be
connected to ground at the UPS (see NEC 250-5d, 250-26, 250.91, 250.92).
GXT6000T-208 CONNECTIONS
CONNECTION
CURRENT
RATING
Recommended
Wire Size
Recommended External
Overcurrent Protection
INPUT 28 AMPS 8 AWG (10 mm²) 40 AMPS
OUTPUT 26 AMPS 8 AWG (10 mm²)
BATTERY 23 AMPS 8 AWG (10 mm²)
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
GXT10000T-208 CONNECTIONS
CONNECTION
CURRENT
RATING
Recommended
Wire Size
Recommended External
Overcurrent Protection
INPUT 45 AMPS 6AWG (16 mm²) 60 AMPS
OUTPUT 43 AMPS 6AWG (16 mm²)
BATTERY 37 AMPS 6AWG (16 mm²)
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
INPUT
UTILITY
OUTPUT
NOTE 4
OPTIONAL
BATTERY
L
1
L
2
L
1
L
2
+ -
NOTE 5
NOTE 6
INPUT TO UPS
NOTE 1
OUTPUT TO LOAD
NOTE 2
OPTIONAL
BATTERIES
NOTE 3
208
208