Liebert UPS Power Supply User Manual


 
7
INSTALLATION
These instructions are for use by competent personnel only.
INSTALLATION CONSIDERATIONS
Detailed instructions to help you install the UPS are provided in the following
pages; however, you should give some consideration to the proposed
environment in which the UPS is to be installed, and carry out some preparatory
work.
UNPACKING AND INSPECTION
Follow unloading instructions printed on the carton. Do not discard any
packaging until installation is complete, check that you have removed to a safe
place the user manual, stabilizing brackets, and any other items shipped with the
unit to be used in its installation.
CAUTION: GXT6000 UPS weighs up to 173kg (381lbs) and the GXT10000 UPS
weighs up to 287kg (633lbs). Use adequate handling aids when moving or
installing the UPS. The UPS is fitted with castor wheels for easy movement. Take
care when the UPS is removed from its packing and being wheeled across an
uneven floor without the stabilizers fitted, that it does not tip over.
Before you install the UPS, give it a thorough visual examination to ensure it has
not been subjected to shipping damage. If it is not in perfect condition, you
should advise both the shipper and the supplier immediately. DO NOT ATTEMPT
TO INSTALL A DAMAGED UPS.
IMPORTANT - Check the UPS rating plate that the UPS is suitable for operation
on your UTILITY voltage and load voltage requirements before installing.
LOCATION
Locate the UPStation GXT indoors in a controlled environment, where it cannot
be accidentally disconnected. Locate it in an area with unrestricted airflow, away
from water, flammable liquids, gases, corrosives, or conductive contaminants.
Air vents are located at the front and the rear of the UPS. Do not position the
UPS in an enclosed space where airflow is restricted. Allow at least 150mm (6
inches) free space around the UPS, with a minimum of 300mm (12 inches) at the
back to enable easy operator access to the rear panel mounted
input/output/battery circuit breakers.
Electrical maintenance/servicing requires access to all four sides of the UPS,
provide the necessary free space or use a flexible wiring system to allow the
UPS to be pulled forward.
Maintain an ambient temperature range of 0 - +40° centigrade (32-104° F)
NOTE- UPS operation in temperatures above 25°C (77°F) reduces battery life.