Liebert UPS Power Supply User Manual


 
31
TROUBLESHOOTING GUIDE
PROBLEM CAUSE SOLUTION
Fault indicators and all
load level LED's are
illuminated
UPS overloaded or load
equipment is faulty
Check load level display and
remove non-essential loads.
Recalculate load VA and
reduce number of loads
connected to UPS. Check load
equipment for faults.
Fault indicators and
diagnostic LED A are
illuminated
UPS internal fan has a
problem or UPS
shutdown due to
temperature condition.
Load is on bypass
power.
Press Alarm silence button.
Ensure that there are no
obstructions in front panel
vents or on rear panel fans;
and UPS is not overloaded.
Once the temperature is
reduced, the UPS will restart
and transfer the connected
equipment to inverter power
automatically.
Fault indicators and
diagnostic LED B are
illuminated
UPS internal DC bus
over voltage
UPS requires service. Contact
your dealer or technical
support.
Fault indicators and
diagnostic LED D are
illuminated
UPS PFC fault. UPS requires service. Contact
your dealer or technical
support.
Fault indicators and
diagnostic LED E are
illuminated
UPS inverter fault. UPS requires service. Contact
your dealer or technical
support.
Fault indicators and
diagnostic LED A & C
are illuminated
UPS failed the battery
test.
Replace batteries. Contact
your dealer or technical
support.
Fault indicators and
diagnostic LED C & E
are illuminated
UPS shutdown due to a
command from the
communications port(s)
Your UPS has received a
signal or command from the
attached computer. If this was
inadvertent, ensure the
communication cable used is
correct for your system. For
assistance, contact your dealer
or technical support.