Liebert XDK-W Network Card User Manual


 
CoolTherm
Manual / Bedienungsanleitung
CoolTherm 01_998_330_0_k page / Seite 13/83
Data overview CoolTherm Table A
General data
Spread chilled water: 12 / 18°C (nominal conditions) Maximum operation pressure heat exchanger: 10 bar
Air temperature to server: 22°C Maximum absolute humidity on site : 8g/kg
Connection heat exchanger: 1“ female threat Colour code for standard colours: x = 8 = RAL 7021 (black grey)
Connection condensate tray: 5/8“ condensed water hose connection x = 1 = RAL 7035 (light grey)
Item
no.
Effective
cooling
capacity
U
(useable)
Height
Width
Depth [D]
Useable depth
[d]
Weight
Recirculated
air flow rate in
cabinet
Electrical connection data
voltage / currency / power
frequency
Fuse / supply
kW mm mm mm mm kg m³/h
V / A / Watt
Hz
A / mm²
08.006.001.x
12 29
1800 700 1200
08.006.002.x
12 33
2000 700 1200 740 290 2.000 200 to 264 / 7 / 1000
50 / 60
16 / 3 x 2,5
08.006.003.x
12 38
2200 700 1200
08.006.006.x
12 29
1800 700 1300
08.006.007.x
12 33
2000 700 1300 840 295 2.000 200 to 264 / 7 / 1000
50 / 60
16 / 3 x 2,5
08.006.008.x 12 38 2200 700 1300
08.006.012.x
17 35
2000 800 1200
08.006.013.x
17 40
2200 800 1200 740 310 3.100 200 to 264 / 8 / 1400
50 / 60
16 / 3 x 2,5
08.006.014.x
17 44
2400 800 1200
08.006.022.x
17 35
2000 800 1300
08.006.023.x
17 40
2200 800 1300 840 320 3.100 200 to 264 / 8 / 1400
50 / 60
16 / 3 x 2,5
08.006.024.x
17 44
2400 800 1300
08.006.033.x
25(35) 37
2200 800 1200 740 340 4.500 200 to 264 / 8 / 1800
50 / 60
16 / 3 x 2,5
08.006.034.x
25 (35) 42
2400 800 1200
08.006.043.x
25 (35) 37
2200 800 1300 840 350 4.500 200 to 264 / 8 / 1800
50 / 60
16 / 3 x 2,5
08.006.044.x 25 (35) 42 2400 800 1300