CoolTherm
Manual / Bedienungsanleitung
CoolTherm 01_998_330_0_k page / Seite 30/83
The fan is installed in the reverse order of removal.
- Tighten the fan fixing bolts.
- Connect the power supply cable to the fan
- Attention: Reconnect earth cable at the sheet steel cover !
- Switch on the the fuse
Dispose of the old fans correctly!
Regularly inspect the heat exchanger (annually)
- Check heat exchanger on air side for soiling and damage.
- Check feed and return for correct function.
- If necessary clean the air side.
- Regularly check odour trap (external) for correct function.
- Heat exchanger can be pulled out for improved cleaning.
- Regularly visually inspect the water circuit for leaks.
Step 4:
Undo the four
fastening bolts
Step 3:
Disconnect
supply cable
at the fan
terminal block
(unscrewing 2
screws and
remove
connector)