Page 18 - 34007532EN/AA
3. Operation
Personalisable function
Rated UPS voltage
Frequency mode
Rated UPS frequency
UPS tolerance for AC-power
source frequency
Overload alarm threshold
UPS restart following short-circuit
Default setting
230 V
Autoselect
F = 50 Hz
F ± 5%
110%
Disabled
Options
200 V - 208 V - 220 V - 240 V - 250 V
Converter
60 Hz
F ± 1% to ± 10%, in 1% steps
0 to 110%, in 10% steps
Enabled (click to add check)
Personalisable function
Transfer to bypass if overload
Transfer to bypass following a fault, whatever the
conditions on the AC-power source
Default setting
Enabled
Disabled
Options
Disabled (click to remove check)
Enabled (click to add check)
"Output" tab
"Bypass" tab
3.5 UPS shutdown
Press button 16 (return to the OFF position).
The connected equipment is no longer supplied with power.
test
1
2
BYPASS
16