34007532EN/AA - Page 25
6. Appendices
6.1 Technical characteristics
Rating
AC input
◗ Voltage
◗ Frequency
◗ Power factor
Output
◗ Voltage
◗ Frequency
◗ Harmonic distortion
◗ Overload capacity
Battery
Environment
◗ Noise level
◗ Operating temperature
◗ Relative humidity
Standards and certification
◗ Safety
◗ Performance
◗ EMC
◗ Marking
Pulsar EXtreme 2200C
2200 VA / 1540 W
Pulsar EXtreme 3200C
3200 VA / 2080 W
Single phase, 120 V / 140 V / 160 V to 284 V
(1)
50/60 Hz (auto-selection)
≥ 0.95
Single phase, 230 V ± 3%
(2)
50/60 Hz ± 5%
(3)
< 4% for linear loads, < 6% for non-linear loads
110% continuous, 130% for 12 seconds, > 130% for 1.5 seconds
6 x 12 V - 7 Ah,
sealed lead-acid, maintenance free
6 x 12 V - 9 Ah,
sealed lead-acid, maintenance free
< 50 dBA
0 to 40°C
20 to 90% (without condensation)
IEC/EN 62040-1-1, EN 60950-1 (RD)
IEC/EN 62040-3
EN 50091-2/IEC 62040-2 class B
IEC 61000-4-2/-3/-4/-6-8/-11, IEC 61000-3-2/-3
CE, TÜV/GS, UL, cUL, CB report
(1) Values indicated for 33%, 66% and 100% of UPS rated output.
(2) Adjustable from 200 V to 250 V using UPS Driver software.