MGE UPS Systems 3200C Power Supply User Manual


 
34007532EN/AA - Page 25
6. Appendices
6.1 Technical characteristics
Rating
AC input
Voltage
Frequency
Power factor
Output
Voltage
Frequency
Harmonic distortion
Overload capacity
Battery
Environment
Noise level
Operating temperature
Relative humidity
Standards and certification
Safety
Performance
EMC
Marking
Pulsar EXtreme 2200C
2200 VA / 1540 W
Pulsar EXtreme 3200C
3200 VA / 2080 W
Single phase, 120 V / 140 V / 160 V to 284 V
(1)
50/60 Hz (auto-selection)
0.95
Single phase, 230 V ± 3%
(2)
50/60 Hz ± 5%
(3)
< 4% for linear loads, < 6% for non-linear loads
110% continuous, 130% for 12 seconds, > 130% for 1.5 seconds
6 x 12 V - 7 Ah,
sealed lead-acid, maintenance free
6 x 12 V - 9 Ah,
sealed lead-acid, maintenance free
< 50 dBA
0 to 40°C
20 to 90% (without condensation)
IEC/EN 62040-1-1, EN 60950-1 (RD)
IEC/EN 62040-3
EN 50091-2/IEC 62040-2 class B
IEC 61000-4-2/-3/-4/-6-8/-11, IEC 61000-3-2/-3
CE, TÜV/GS, UL, cUL, CB report
(1) Values indicated for 33%, 66% and 100% of UPS rated output.
(2) Adjustable from 200 V to 250 V using UPS Driver software.
(3) Frequency-converter mode can be set using the UPS Driver software.